| SPECIFICATIONS |
| MODEL |
6502 |
6503 |
6505 |
6510 |
6520 |
6530 |
6540 |
| INPUT |
| Phase |
1¢ |
3¢ |
| Voltage |
230Vac±15% |
220/380Vac±10% |
| Frequency |
47-63Hz |
| OUTPUT |
| Power rating |
2KVA |
3KVA |
5KVA |
10KVA |
20KVA |
30KVA |
40KVA |
| Max. Current (r.m.s) |
0-150V |
16.8A |
25.2A |
42.0A |
84.0A |
168.0A |
252.0A |
336.0A |
| 0-300V |
8.4A |
12.6A |
21.0A |
42.0A |
84.0A |
126.0A |
168.0A |
| Phase |
1¢/2W |
| Waveform Distortion |
< 1% at 45-500Hz (Resistive Load) |
| Crest Factor |
> 3 |
| Load Regulation |
± (0.5% of output +0.5V) at Resistive Load |
| Response Time |
< 2 msec |
| SETTINGS |
| Voltage |
Range |
0-150V/0-300V Selectable |
| Resolution |
0.1V |
| Accuracy |
±(1% of setting + 2counts) |
| Frequency |
Range |
45-500Hz Full Range Adjust |
| Resolution |
0.1Hz at 45-99.9Hz , 1Hz at 100-500Hz |
| Accuracy |
±0.02% of setting |
| MEASUREMENT |
| Voltage |
Range |
0.0-300.0V |
| Resolution |
0.1V |
| Accuracy |
± (1% of reading + 2counts) |
| Frequency |
Range |
0.0-500.0Hz |
| Resolution |
0.1Hz |
| Accuracy |
±0.1Hz |
| Current (r.m.s) |
Range |
L |
0.000-3.500A |
0.00-35.00A |
| H |
3.00-35.00A |
30.00-350.0A |
| Resolution |
L |
0.001A |
0.01A |
| H |
0.01A |
0.1A |
| Accuracy |
L |
± (1% of reading +5counts) |
± (1% of reading + 2counts) |
| H |
± (1% of reading +1count) |
± (1% of reading +1count) |
| Power |
Range |
L |
0.0-350.0W |
0.000-3.500KW |
| H |
300-4000W |
3.00-40.00KW |
| Resolution |
L |
0.1W |
0.001KW |
| H |
1W |
0.01KW |
| Accuracy |
L |
± (1.5% of reading +5counts) |
± (1.5% of reading +5counts) |
| H |
± (1.5% of reading +1count) |
± (1.5% of reading +1count) |
| Power Factor |
Range |
0.000-1.000 |
| Resolution |
0.001 |
| Accuracy |
Calculated and displayed to three significant digits |
| GENERAL |
| PLC Remote |
I/P:ON/OFF, P1, P2, P3, O/P:Processing |
| Memory |
8 Memoies, 5steps per memory for Voltage, Frequency, Test Time, Delay time and
Current, Power, Power Factor Hi, Lo Limit setting. |
| Timer |
0=Continuous, 1-9999 (Unit: sec, minute, hour selectable) |
| Auto Loop Cycle |
0=Continuous, OFF=Loop Once, 2~9999 (Unit:×1, ×10, ×100) |
| Auto Voltage Adjust |
Enable it for improve voltage regulation within ±0.1V |
| Efficiency |
≧80%(at Full Load ) |
≧85%(at Full Load ) |
| Protection |
Over Load , Short Circuit , Over Temperature |
| Calibration |
Front Panel Calibration |
| Interface (Option) |
GPIB/RS232 |
| Dimension (W×H×D) mm |
430×306×650, 5U |
430×306×650, 5U |
430×306×650, 5U |
430×729×650, 14U |
430×863×650, 17U |
600×1085×900, 22U |
600×1085×900, 22U |
| Net Weight |
60Kg |
65Kg |
80Kg |
200Kg |
315Kg |
465Kg |
550Kg |
| product specifications are subject to change without notice. |